NewsFiOC-32 coming soon: Sedona controller with local display and dual Ethernet

Controllers In stock

FiOC-40

40-point Sedona controller that runs the application on the device

A 40-point DIN-rail controller that runs its control application on the device with Sedona. It talks to field devices and supervisory systems over Modbus, BACnet and MQTT, and is programmed live with Coselium Workbench or Niagara N4.

I/O channels: 40

Price on request

  • BACnet/IP
  • BACnet MS/TP
  • Modbus TCP
  • Modbus RTU
  • MQTT
  • Sedona / SOX
  • Niagara N4
  • BLE
FiOC-40 controller, front three-quarter view

Use the arrows to move between images; press Esc to close.

1 / 6

Overview

FiOC-40 brings the local I/O of an automation panel and its control logic into one housing. The application is built from point-based Sedona components and runs on the device, so field logic keeps working even when the supervisory link is down.

Programming

Applications are edited live over SOX with Coselium Workbench: components are added, wired and monitored while the device runs. In Niagara N4 projects the Coselium Niagara modules connect to the device directly or integrate it through a station driver.

Communication

Communication is defined by the kits added to the application. The controller has no fixed register table; addresses and objects are set up per project. Modbus TCP/RTU master and slave, BACnet/IP, BACnet MS/TP and MQTT (optional TLS) are supported. With an optional licence the device also routes between BACnet/IP and MS/TP networks.

Service

  • Local web interface in six languages: status, I/O settings, network, files and software update
  • Short-range commissioning from a mobile device over Bluetooth LE
  • Application manager with backup and restore
  • Open-circuit, short-circuit and out-of-range detection on sensor inputs

Highlights

  • 40 physical points: 16 DI (DI1–DI4 counters), 8 UI, 8 relay DO, 8 FIO
  • Sedona application on the device, live programming over SOX
  • Modbus TCP/RTU master and slave, BACnet/IP, BACnet MS/TP, MQTT (TLS)
  • Optional BACnet/IP ↔ MS/TP router licence
  • Works with Coselium Workbench and Niagara N4 (cosel module)
  • Local web interface, BLE commissioning, hardware RTC

Typical applications

  • Starting and stopping air handling units, pumps, boilers and chillers in the right order
  • Energy monitoring, alarms and status tracking
  • Automation panels that need schedules and local logic
  • Control stations collecting field devices over Modbus, BACnet or MQTT

Specifications

I/O channels
16 × DIDirect/reverse; DI1–DI4 also pulse counters
8 × UI0–10 V, 2–10 V, 0/4–20 mA, dry contact, NTC (7 types), PT1000, NI1000, resistance
8 × DORelay; 5 A @ 277 Vac / 3 A @ 30 Vdc resistive
8 × FIO0–10 V / 2–10 V analogue output, digital output or digital input
Hardware
ProcessorESP32-S3
Physical points40 (16 DI, 8 UI, 8 DO, 8 FIO)
UI resolution22 bit
Communication
Ethernet1 × RJ45, 10/100 Mbit/s
Serial port1 × RS-485
WirelessBluetooth LE (service and commissioning)
BACnet vendor ID1596
Electrical
Supply24 Vac ±20% or 21–30 Vdc, Class 2
Nominal consumption5 VA
Relay output5 A @ 277 Vac / 3 A @ 30 Vdc (resistive)
FIO analogue output0–10 V or 2–10 V, max. 20 mA per channel
Mechanical & environment
ProtectionIP20, T50
Operating0–50 °C, 5–95% RH (non-condensing)
Storage-20–70 °C, 5–95% RH (non-condensing)
MountingDIN rail (EN 60715, 35 mm)
Dimensions (W × H × D)175 × 112 × 60 mm
Software
RuntimeSedona virtual machine on the device
ProgrammingCoselium Workbench (SOX), Niagara N4 (Coselium Niagara modules)
Service interfacesWeb (HTTP), BLE, SOX/DASP (UDP 1876)
LicensingLocal I/O, Modbus and BACnet components with the device licence; BACnet router as an optional add-on
Network & service
Factory IP192.168.1.160/24