FiO-40

40-point Modbus / BACnet remote I/O, no programming required

A 40-point remote I/O module that connects to a supervisory system without programming, using a fixed Modbus register map and BACnet object model. Depending on the licence level it also acts as a Modbus gateway or BACnet router.

I/O channels: 40

Price on request

  • BACnet/IP
  • BACnet MS/TP
  • Modbus TCP
  • Modbus RTU
  • BLE
FiO-40 remote I/O module, front three-quarter view

Use the arrows to move between images; press Esc to close.

1 / 6

Overview

FiO-40 is built for adding field points to an existing BMS or controller. Channel structure and addresses are fixed: the integrator takes the register and object list from the reference appendix and maps it straight into the supervisory system.

Protocols

One field protocol runs at a time: Modbus RTU/TCP slave or BACnet/IP / BACnet MS/TP. On Modbus, function codes FC01, FC03, FC05, FC06, FC15 and FC16 are supported; analogue values are fixed-point and UI values can also be read as float32.

Licence levels

  • Base: Modbus RTU/TCP and BACnet/IP, BACnet MS/TP
  • Level 1: Modbus TCP ↔ RTU gateway
  • Level 2: Modbus gateway and BACnet/IP ↔ MS/TP router

Fail-safe behaviour

When communication is lost, outputs fall back to default values defined per channel. Settings are made from the local web interface or from a mobile device over Bluetooth LE; software updates are installed over the air.

Highlights

  • 40 physical points: 16 DI (DI1–DI4 counters), 8 UI, 8 relay DO, 8 FIO
  • Modbus RTU/TCP slave or BACnet/IP / BACnet MS/TP
  • Level 1 licence: Modbus TCP ↔ RTU gateway
  • Level 2 licence: Modbus gateway + BACnet/IP ↔ MS/TP router
  • Fixed register map and BACnet object model
  • Per-channel output defaults on communication loss

Typical applications

  • I/O expansion in AHU, pump, boiler and chiller panels
  • Adding dry contacts, analogue sensors and universal points to an existing BMS
  • Driving damper and valve actuators, relays and contactors
  • Fast retrofit integration through a fixed Modbus/BACnet map

Specifications

I/O channels
16 × DIDirect/reverse; DI1–DI4 also pulse counters
8 × UI0–10 V, 2–10 V, 0/4–20 mA, dry contact, NTC (7 types), PT1000, NI1000, resistance
8 × DORelay; 5 A @ 277 Vac / 3 A @ 30 Vdc resistive
8 × FIO0–10 V / 2–10 V analogue output, digital output or digital input
Hardware
ProcessorESP32-S3
Physical points40 (16 DI, 8 UI, 8 DO, 8 FIO)
UI resolution22 bit
Communication
Ethernet1 × RJ45, 10/100 Mbit/s
Serial port1 × RS-485
WirelessBluetooth LE (service and commissioning)
BACnet vendor ID1596
Electrical
Supply24 Vac ±20% or 21–30 Vdc, Class 2
Nominal consumption5 VA
Relay output5 A @ 277 Vac / 3 A @ 30 Vdc (resistive)
FIO analogue output0–10 V or 2–10 V, max. 20 mA per channel
Mechanical & environment
ProtectionIP20, T50
Operating0–50 °C, 5–95% RH (non-condensing)
Storage-20–70 °C, 5–95% RH (non-condensing)
MountingDIN rail (EN 60715, 35 mm)
Dimensions (W × H × D)175 × 112 × 60 mm
Network & service
IPIPv4, static or DHCP, mDNS (fio-40.local)
Factory IP192.168.1.160/24
Service interfacesPassword-protected web UI, REST API, BLE, OTA update
Modbus function codesFC01, FC03, FC05, FC06, FC15, FC16