System architecture

Eight typical setups Coselium devices are used in: what connects to what, over which line and protocol. Values are the factory defaults from the product datasheets.

Setup A

FiOC-40 as the panel controller

In an AHU, pump set, boiler or chiller panel the control logic runs on the FiOC-40 as a Sedona application. Sensors and outputs are wired to the terminals; devices such as energy meters or drives are read over the RS-485 line with Modbus RTU. The application is edited live with Coselium Workbench, and initial settings can be made on site from a phone over BLE.

FiOC-40 integration topology diagram
FiOC-40 integration topology (from the product documentation).
Setup A connections
FromToLineProtocol / setting
Temperature, humidity and pressure sensorsFiOC-40 UITerminalsNTC, PT1000, NI1000, 0–10 V, 4–20 mA
FiOC-40 FIO / DOValves, dampers, pumps and fansTerminals0–10 V / 2–10 V analogue output, relay
FiOC-40Energy meter, driveRS-485Modbus RTU master, 9600 8N1
Engineering PCFiOC-40EthernetCoselium Workbench, SOX (UDP 1876)
PhoneFiOC-40Bluetooth LEMobile commissioning

Setup B

Adding points to an existing BMS: FiO-40

FiO-40 is a remote I/O that needs no programming. With its fixed Modbus register map and BACnet object model it connects directly to an existing BMS or controller; in retrofits it adds dry contacts, analogue sensors and outputs. One protocol runs on site at a time: Modbus or BACnet. If communication is lost, outputs go to per-channel default values.

FiO-40 communication topology diagram
FiO-40 communication topology (from the product documentation).
Setup B connections
FromToLineProtocol / setting
BMS / SCADAFiO-40EthernetModbus TCP (port 502) or BACnet/IP (UDP 47808)
ControllerFiO-40RS-485Modbus RTU slave (9600 8N1) or BACnet MS/TP (38400)
Contacts, sensors, metersFiO-40 DI / UITerminalsDI1–DI4 can also be pulse counters

Setup C

I/O expansion: FiOC-40 and FiO-40

When a panel needs more than 40 points, the control logic stays on the FiOC-40 and the extra points come from FiO-40 modules. The FiOC-40 reads and writes the FiO-40s as a Modbus master: Modbus RTU on the RS-485 line or Modbus TCP over Ethernet. Because the FiO-40 register map is fixed, nothing is programmed on the FiO-40 side. Planning allows up to four FiO-40s per FiOC-40; Configurator, the tool our dealers use, distributes points over the devices by this rule. The supervisory system sees the FiO-40 points through the FiOC-40.

I/O expansion topology with FiOC-40 and FiO-40
FiOC-40 with FiO-40 expansion: Modbus over RS-485 or Ethernet.
Setup C connections
FromToLineProtocol / setting
FiOC-40FiO-40 (RTU address 1–4)RS-485Modbus RTU master → slave, 9600 8N1
FiOC-40FiO-40EthernetModbus TCP master → FiO-40, port 502
FiOC-40 applicationBMS / NiagaraEthernetModbus TCP slave, BACnet/IP or cosel modules
Engineering PCFiOC-40EthernetCoselium Workbench, SOX (UDP 1876)

Setup D

RS-485 field devices: drives and energy meters

The FiOC-40 works as a Modbus RTU master on the RS-485 line. Modbus RTU devices such as variable frequency drives and energy meters are daisy-chained on the same line, each with its own slave address. Line speed is 2400–115200 baud with no, odd or even parity; the default is 9600 8N1. One serial protocol runs on the line at a time. Termination (EOL) is switched on at the devices at both ends of the line, BIAS is selected on a single mid-line device on long lines and the rest stay OFF; on Coselium devices this is a three-position switch next to the RS-485 terminals. The values read are used in the application and can be served to the supervisory system over Modbus slave or BACnet.

Modbus RTU field devices on the FiOC-40 RS-485 line
Modbus RTU devices on the FiOC-40 RS-485 line and the BIAS/EOL setting.
Setup D connections
FromToLineProtocol / setting
FiOC-40Drives, energy meterRS-485Modbus RTU master, a slave address per device
Line start (FiOC-40) and last device—RS-485BIAS/EOL: EOL at both ends, OFF in between
BMS / SCADAFiOC-40EthernetModbus TCP slave (port 502) or BACnet/IP (UDP 47808)

Setup E

Bringing MS/TP devices onto BACnet/IP: router

BACnet MS/TP devices such as fan-coil thermostats are connected to the FiOC-40 RS-485 line. When BACnet/IP and MS/TP are enabled together on the FiOC-40, the device routes between the two networks; the BMS sees the MS/TP devices over BACnet/IP. This is enabled by the optional router feature on top of the base licence. The IP and MS/TP network numbers must differ (default 1 and 2). FiO-40 does the same job with a Level 2 licence.

MS/TP thermostats behind a FiOC-40 BACnet router
FiOC-40 BACnet router: MS/TP thermostats on the BACnet/IP network.
Setup E connections
FromToLineProtocol / setting
BMSFiOC-40EthernetBACnet/IP, UDP 47808, network 1
FiOC-40Fan-coil thermostatsRS-485BACnet MS/TP, 38400 baud, network 2

Setup F

With Niagara N4

Coselium devices connect to Niagara N4 with the cosel module family (Niagara 4.12 and later). There are two paths. If the service PC can reach the device network, the device can be reached directly from Niagara Workbench and the application programmed without setting up a station. If the device must be monitored continuously, the station driver is used: the station finds the device and brings in its points and schedules. Remote access goes through the station. FiO-40 does not connect to Niagara directly: it is connected to a FiOC-40 and its points reach the station through the FiOC-40.

Connecting Coselium devices to Niagara N4
Niagara N4: direct SOX connection and station driver; FiO-40 through the FiOC-40.
Setup F connections
FromToLineProtocol / setting
Niagara WorkbenchFiOC-40EthernetDirect connection (SOX, UDP 1876)
Niagara stationFiOC-40Ethernetcosel station driver: device, points and schedules
FiOC-40FiO-40RS-485Modbus RTU or Modbus TCP; points reach the station through the FiOC-40

Setup G

Joining two lines: FiO-40 gateway and router

Gateway and router functions, enabled by licence, join two lines without a separate network device. With a Level 1 licence the FiO-40 is a Modbus gateway in both directions: a Modbus TCP client on Ethernet reaches the Modbus RTU devices on the RS-485 line (one client at a time), or an external RTU master on the line reaches a Modbus TCP device on Ethernet. A Level 2 licence adds the BACnet/IP ↔ MS/TP router; the IP and MS/TP network numbers must differ.

FiO-40 protocol services: rtu-slave, gateway-server, gateway-client, BACnet ip, mstp and router
FiO-40 protocol services (from the product documentation).
Setup G connections
FromToLineProtocol / setting
Modbus TCP clientModbus RTU devices on RS-485Ethernet ↔ RS-485Modbus TCP → RTU gateway — Level 1
External RTU master on the lineModbus TCP targetEthernet ↔ RS-485Modbus RTU → TCP gateway — Level 1
BACnet/IP networkBACnet MS/TP lineEthernet ↔ RS-485BACnet router — Level 2

Setup H

Sending data to a broker with MQTT

The FiOC-40 connects to an MQTT broker; MQTT needs no licence. Values in the application are published to the broker and writable values take commands through it, so a dashboard, SCADA or another application can monitor values and send settings. Each device is identified on the broker by its serial number. The connection can be protected with TLS (server certificate or mutual TLS); certificates are uploaded from the device web interface. The topic structure is given in the product datasheet; our dealers can assist with the setup.

FiOC-40 MQTT broker connection
FiOC-40 MQTT connection.
Setup H connections
FromToLineProtocol / setting
FiOC-40MQTT brokerEthernetport 1883; 8883 with TLS
FiOC-40Dashboard / SCADAEthernetValue publishing
ApplicationFiOC-40EthernetCommands (writable values)

Ports and factory defaults

InterfaceFunctionDefaultDevice
EthernetModbus TCPport 502FiOC-40, FiO-40
EthernetBACnet/IPUDP 47808FiOC-40, FiO-40
EthernetMQTTport 1883; 8883 with TLSFiOC-40
EthernetWorkbench connection (SOX/DASP)UDP 1876FiOC-40
EthernetWeb interfaceHTTP, port 80FiOC-40, FiO-40
EthernetModbus gateway-serverport 504 (Level 1 licence)FiO-40
EthernetModbus gateway-client target192.168.1.50 / 1502FiO-40
EthernetFactory IP address192.168.1.160/24FiOC-40, FiO-40
RS-485Modbus RTU9600 8N1FiOC-40 (master/slave), FiO-40 (slave)
RS-485BACnet MS/TP38400 baudFiOC-40, FiO-40
Ethernet ↔ RS-485BACnet network numbers (router)IP 1, MS/TP 2FiOC-40, FiO-40
Bluetooth LEMobile commissioning—FiOC-40, FiO-40

Values are factory defaults and are changed per project; the full list is in the product datasheets.

Who installs it?

Design, installation and commissioning are carried out by our partner dealers. For help with product selection or to find a dealer in your region, please contact us.